54 Pump Control Unit Pump Interface Manual v1.3
Gasboy CFN Series 03/20/03
DIP Switch Bank C
Note: In connection with pulser enabled, there are two error codes, each with three characters,
that can show up in the error column on a transaction printout. The reset-failed-to-start
transaction code is $D2 through $DF, and the reset-failed-to-complete transaction code is $E5
through $EF ($ indicates hexadecimal). The last character in each code (2 through F or 5 through
F) is the number of seconds the PCU waited for reset to start or complete. This numeric character
is incremented by one each time the PCU reset-to-start/complete times out, until the maximum
time-out of 15 (15 is F in hexadecimal counting) seconds is reached.
Test Mode. When test mode is activated with switch C-8, switch C-5 determines the relay limits:
In test mode, switches C-6 and C-7 select the pump to be tested:
Address B-1 B-2 B-3 B-4
1 clclclcl
2 opclclcl
3 clopclcl
4opopclcl
5 clclopcl
6opclopcl
7 cl opopcl
8 opopopcl
9 clclclop
10 op cl cl op
11 cl op cl op
12 op op cl op
13 cl cl op op
14 op cl op op
15 cl op op op
16 op op op op
Position & Definition Setting(*=customary)
1-4 pulser enabled (pumps
1-4)
(see note below)
closed=after reset is
complete
open=upon activation
5____
6 dead man timer *always open=enabled
7____
8 test mode *closed=no
open=yes
C-5 Function
open pump slows at 500 pulses and turns off at 510 pulses
closed pump slows at 50 pulses and turns off at 60 pulses
Pump to Test C-6 C-7
1 closed closed
2openclosed
3closedopen
4openopen