Pump Interface Manual v1.3 Gilbarco Interface Unit 29
03/20/03 Gasboy CFN Series
Front Panel LEDs
L1 L12
o o o o o o o o o o o o CPU
o o o Current Loop PCB
DC BOK BAD
Interface Board
Site Controller Configuration
Site Controller I
Site Controller I version 4.0 software and above will work with Gilbarco pumps.
Normally the Site Controller I is configured at the factory for the pump types. The pump types
are configured at TABLE 24, OFFSET 18+(PMP#-1)x4. Refer to the Site Controller I Technical
Manual
to help understand the following CONFIGS.
a) 2 sided, 1 hose per pump. Byte = 64
b) 1 sided, 1 hose per pump. Byte = 74
c) 2 sided, 2 hose per pump. Byte = 65
d) 1 sided, 2 hose per pump. Byte = 75
e) 2 sided, 3 hose per pump. Byte = 66
f) 1 sided, 3 hose per pump. Byte = 76
Note: SC I will not work with multi hose unit.
Lamp Indication
L1 transmit data on CRIND 422/485 port
L2 receive data on CRIND 422/485 port
L3 transmit data on 422/485 loop #1
L4 receive data on 422/485 loop #1
L5 dead man timer refresh
L6 current loop power enabled
L7 current loop #1 active if flashing
L8 current loop #2 active if flashing
L9 program crash code bit 1
L10 program crash code bit 2
L11 program crash code bit 3
L12 program crash code bit 4
DC DC 5V power OK (green)
BOK battery OK (green)
BAD battery bad (red)
Jumper Function and/or Normal Setting
K1 Baud rate clock source; must be installed in position 1.
K2 Battery backup enable. Boards should be stored with this
jumper out; it should be installed at assembly time. Lamp
BAD will light if K2 is omitted.